Transformers Substations

Prefabricated transformers subtations are used in the tri-phase electrical networks and have following advantages

• Easy to transport
• Quick installation
• Reduced maintenance
• 30 years lifetime
• Safety for the personnel and environment

Based on the customer requiest, the substation can be build „walk-in” or „non walk-in” type.

The substation are composed of concrete foundation, water and oil resistant and the cabin, with a natural ventilation system which ensure a protection degree IP54 for medium voltage room and IP45 for the entire substation. Temperatrure class is 10K for transformers up to 400kVA and 20K for transformers over 400kVA.

The design is based on IEC62271-202 standard. In this regard, the homologated product was tested in 2007 at ICMET Craiova Laboratory to internal arc according IEC62271-202 Annex A. The substation was succesfully tested at 16kA/1 sec electric arc for IAC-AB class whic is the highesc class for personnel safety.

OPERATING, TRANSPORT AND STORAGE CONDITION

Climatic zone

N, according STAS 6535/ 83

Operating category

1, according STAS 6692/ 83

Altitude

max. 1000 m

Ambient temperature during operation

min. – 40 °C; max. + 40 °C

Ambient temperature during transport

– 25 °C ÷ + 40 °C

Relative humidity during operation

100% la max. + 25 °C

Relative humidty during transport and storage

80% la + 20 °C

Seismic acceleration ground level

0,5g

Fire resistangce

II

Protection degree

IP 45

Noise level

53dB

The product was tested in at ICMET Craiova Laboratory ccording IEC62271-202 with following test reports :

-No. 10033 – Internal arc test Ip = 40kA, Ik = 16kA, tk = 1s, IAC-AB;

-No 10039 – Thermal and dynamic test for low voltage, medium voltage and grounding circuits;

-No 10037 – Thermal class of the envelope

-No 10033 – Noise level test

TRANSFORMER SUBSTATION SUPPLIED ACCORDING TO ENEL DG2061 REGULATIONS EDITION 1 AND EDITION 2

Construction characteristics:

– Length: 4m;  

– Width: 2,44 m

TRANSFORMER SUBSTATION SUPPLIED ACCORDING TO ENEL DK5600 REGULATIONS

Dimensions:
– Lenght: 6.5 m; 

– Width: 2.5 m

TRANSFORMER SUBSTATIONS SUPPLIED WITH 2 TRANSFORMERS

Construction characteristics:
– Length: 8,5 m; 

– Width: 2,5 m

TRANSFORMER SUBSTATION WITH EXTERNAL OPERATION

Construction characteristics:
– Length: 3.5 m
– Width: 1.4 m

TRANSFORMER SUBSTATIONS FOR ENERGY PRODUCERS

Construction characteristics:
– Length: 8.5 m
– Width: 2.5 m